Possible
Cause 1: A "black dot label" (emissivity sticker)
is not being used during Thermal Stimulator calibration verification.
What
to do: Locate the emissivity sticker, which looks like
a black dot, and repeat the calibration verification procedure
(described in the Service Bulletin CASE4-B08, or on pages
6.4 and 6.4-b of the Hardware User's Guide).
Possible
Cause 2: Thermal Stimulator is not correctly connected to
Main Unit.
What
to do: Verify that the blue constantan-copper plug (Thermal
Stimulator connector B) and the round connector (Thermal
Stimulator connector A) are correctly installed. Refer to
chapter 4 of the CASE IV System Hardware User's Guide for
set-up instructions. Verify that the hoses are attached
to the Thermal Reservoir.
Possible
Cause 3: Batteries in the voltmeter or infrared thermometer
are low.
What
to do: Check the batteries in the voltmeter and the
infrared thermometer. Refer to the "Thermal Stimulator
Calibration Check" section in chapter 6 of the CASE
IV System Hardware User's Guide for battery specifications.
Note:
The infrared thermometer has a high current draw on the
battery. If left on for an extended period the battery will
be below specifications and will need to be replaced.
Possible
Cause 4: Ambient temperature of testing room is out of the
acceptable range.
What
to do: Verify that the temperature of the testing room
is not under 24°C/75.2°F or over 26°C/78.8°F. If the ambient
temperature is out of range, adjust the room temperature.
It is important to keep the room at a constant temperature
at all times. Allow the equipment to stabilize after each
ambient temperature change.
Possible
Cause 5: Temperature of the water in the Thermal Reservoir
is out of the acceptable range.
What
to do: Verify the temperature of the water in the reservoir
is not under 24°C/75.2°F or over 26°C/78.8°F. Heat up or
cool down the water accordingly.
Note:
After changing the temperature of the reservoir, you must
allow a minimum of 15 minutes or more to allow the water
in the system to circulate and be uniform throughout.
Possible
Cause 6: Water is not flowing through the Thermal Stimulator
system.
What
to do: Take the top off the Thermal Reservoir and lift
the hose. Verify that water is flowing through the hose
and that the water level is between the fill lines. If the
water is too high or too low, adjust accordingly. If water
is not flowing through the hose, look into the following:
1.
Check that the Thermal Reservoir is plugged into the plug
strip (or isolation transformer).
2.
Is the water in the tank old or dirty? If so, the water
in the reservoir should be replaced. (Replace the water
at least every 90 days.)
3.
With the Thermal Stimulator attached, blow out the hose
with compressed air at low pressure (10 to 20 pounds per
square inch, or psi). This may clear the hose of any blockages
that restrict water flow.
Note:
The use of a bactericide in the water is recommended to
help control the bacterial/algae growth, which can adversely
affect the performance of the system.
Possible
Cause 7: Temperature of Thermal Stimulator hardware is outside
of the acceptable range.
What
to do: Check the temperature of the Thermal Stimulator's
ceramic plate by doing the following:
1.
With the CASE IV System on, exit from any calibration verification
procedures or tests.
2.
Ensure that the system has been on for at least 15 minutes.
3.
Place the Thermal Stimulator and the infrared thermometer
in the Thermal Calibration Fixture, as if performing calibration
verification.
4.
Allow the temperature on the infrared thermometer to stabilize,
and verify the temperature is not under 24°C/68°F or over
26°C/72°F. If not within range, see possible cause 4.
RETURN
TO TOP
Possible
Cause 8: Calibration of the voltmeter or infrared thermometer.
What
to do: Check the calibration sticker on these items
to verify that the calibration periods have not expired.
Note:
It is recommended that these items be calibrated to NIST
standards at least once per year.
Possible
Cause 9: The voltmeter or infrared thermometer is out of calibration,
even though date on the sticker indicates the calibration
period has not expired.
What
to do: Point the infrared thermometer at something that
is exactly 0°C. For example, put cold water and ice cubes
in a dark-colored container (such as a black ceramic coffee
cup). Point the infrared thermometer at the water, and verify
that the reading on the voltmeter is 0°C.
Possible
Cause 10: Temperature readings are being taken at the wrong
time.
What
to do: Are you examining the temperature reading after
selecting "Set Aluminum Block to 30 Degrees Celsius"?
This routine warms up the stimulator, and readings are not
supposed to be taken during this step. Check the calibration
at 30 degrees using the "Thermal 30 Degree Test."
Review the calibration verification procedure in the Hardware
User's Guide.
Possible
Cause 11: The stimulator and infrared thermometer are not
properly positioned in the Thermal Calibration Fixture.
What
to do: Make sure white ceramic face of the Thermal Stimulator
is directed inward toward the square hole in the fixture,
and make sure both the Thermal Stimulator and the infrared
thermometer's probe are fully seated as far as they will
go.
Possible
Cause 12: All the hardware is too cold.
What
to do: This situation is typical if the unit has just
been set up after being stored in a cool truck, airplane,
or storage room. Set up the unit and leave it on for 24
hours to bring all the components and electrical parts up
to operating temperature.
Possible
Cause 13: Poor connection on constantan-copper plug.
What
to do: Unplug and reconnect the blue constantan-copper
plug (Thermal Stimulator connector B) several times. Using
an eraser, remove any oxidation that may have occurred.
Possible
Cause 14: The Thermal Stimulator may be defective.
What
to do: Contact your help desk for repair instructions.